W-2WAY ECO-i SYSTEM
Outdoor Unit Repair Procedures
4. Backup Operation
4-2-2. Backup operation by setting the failed compressor not to operate
Backup operation settings for each compressor
INV compressor AC1 compressor AC2 compressor Setting for backup operation
OK OK Failed DIP switch S010:
Turn BACK UP and AC2 ON.
OK Failed OK DIP switch S010:
Turn BACK UP and AC1 ON.
OK Failed Failed DIP switch S010:
Turn BACK UP, AC1, and AC2 ON.
Failed OK OK DIP switch S010:
Turn BACK UP and INV ON.
Failed OK Failed DIP switch S010:
Turn BACK UP, INV, and AC2 ON.
Failed Failed OK DIP switch S010:
Turn BACK UP, INV, and AC1 ON.