EasyManua.ls Logo

Sanyo C4232 - Outdoor Unit Major Component Specifications

Sanyo C4232
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 12 –
SM830078
(2) Major Component Specifications
(B) Outdoor Unit
2. SPECIFICATIONS
+ 2.0
+ 0.5
DATA SUBJECT TO CHANGE WITHOUT NOTICE
MODEL No. C4232
Source 230 - 208 V / 1 phase / 60 Hz
Compressor Scroll (Hermetic)
Model ZR47KC - PFV
Source 230 - 208 V / 1 phase / 60 Hz
Nominal output W 4,270
Compressor oil cc 1,240
Coil resistance (Ambient temperature 77 °F) R - W : 0.475 , S - W : 1.850
Safety device Internal type
Overload relay models
Operating temperature Open °F 320 ± 9
Close °F 189 ± 20
Operating ampere (at 77 °F) A
Run capacitor VAC, µF 400 V, 50 µF
Refrigerant amount charged at shipment lbs. (kg) R22 : 9.7 (4.4)
High pressure switch ACB - 1UB11
Set pressure OFF kg/cm
2
30
ON kg/cm
2
24 ± 2.0
Fan Propeller
Number...diameter in. (mm) 1 … 18-3/32 (460)
Fan speeds 2 (AUTO)
Fan motor
Model KFC6T - 91D6P × 2
Source 230 - 208 V / 1 phase / 60 Hz
No. of pole … rpm (230 V, High) rpm 6 … 879
Nominal output W 110 × 2
Coil resistance BRW WHT : 67.14 , VLT YEL : 11.42
(Ambient temperature 68 °F)
WHT VLT : 64.85 , YEL PNK : 10.60
Safety device
Operating temperature Open °F248± 9
Close °F171± 27
Run capacitor VAC, µF 440 V, 4 µF × 2
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows … Fins per inch 2 … 12.7
Face area ft.
2
(m
2
) 11.63 (1.08)