4. Backup Operation
W-2WAY ECO-i SYSTEM
Outdoor Unit Repair Procedures
4-2-2. Backup operation by setting the failed compressor not to operate
Backup operation settings for each compressor
INV compressor AC1 compressor Setting for backup operation
OK Failed
DIP switch S010:
Turn BACK UP and AC1 ON.
Failed OK
DIP switch S010:
Turn BACK UP and INV ON.
Failed Failed
DIP switch S010:
Turn BACK UP, INV, and AC1 ON.