5
G Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary.
Max. Max. Allowable Total Limit of Limit of Elevation Required Amount
Allowable Tubing Length Total Tubing Length Difference of Additional
Model Tubing Length at shipment (L1+L2+L3) or (H1, H2, H3, H4) Refrigerant
per unit (L1+L2+L3) or (L1+L2+L3+L4) (ft.) (oz./ft.)*
(ft.) (L1+L2+L3+L4) (ft.)
(ft.)
CM1972/CLM1972 82 150 (L1+L2+L3) 150 (L1+L2+L3) 50
CM2472/CLM2472 82 150 (L1+L2+L3+L4) 200 (L1+L2+L3+L4) 50 0.22
CM3172/CLM3172 100 150 (L1+L2+L3+L4) 230 (L1+L2+L3+L4) 50 0.22
06-060 KMS0772-2472 ENG 3/17/06 2:50 PM Page 5