EasyManua.ls Logo

Sanyo MDF-U500VX - Cooling Circuit Diagnosis; Normal Mode Diagnosis Procedures; ECO Mode Diagnosis Procedures

Sanyo MDF-U500VX
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 32 -
8. Diagnosis of abnormal cooling circuit
(1) Normal mode
㽲㩷 Frequency: Diagnosis is performed for once per day (2:00a.m. or later) on either compressor A and B.
Diagnosis of compressor A is done first.
(Ex.) After the power is supplied, diagnosis of compressor A is performed at 2:00a.m. or later.
Diagnosis of compressor B is performed the next day.
㽳㩷 2 portions of pull-up time just before diagnosis ( indicated in the picture below) are stored.
Calculation of period for diagnosing cooling circuit: (ǻT1+ǻT2)/2x1.1 (Ԛ indicated in the picture below)
Diagnosis pattern
a. When unit reaches set temp -2.0 beyond the OFF point (set temp -0.6) during a single compressor
cycle, the diagnosis is considered Normal that the unit can keep cooling performance.
(Line-a indicates in the picture below)
b. When unit keeps temperature almost near set temp and diagnosis period expires, the diagnosis is
considered Normal that the unit can keep cooling performance.
(Line-b indicates in the picture below)
c. When unit reaches the ON point (set temp +0.6) during diagnosis, the diagnosis is considered
Abnormal that the unit cannot keep cooling performance because temperature increases is the same
as pull-up temperature except in cycle operation. (Line-c indicates in the picture below)
ĺ Diagnosis will be performed again 48 hours later and it will be determaind as a failure in cooling
circuit if the results are the same.
ON
Set temp+0.6㷄䋩
Chamber temp
OFF
(Set temp-0.6)
Diagnosis OFF
(Set temp-2.0)
Comp
Comp
of
f
of
f
on
on
of
f
of
f
on
on
Pull-up time
㰱㪫㪈
Pull-up time
㰱䌔㪉
of
f
on
Diagnosis period
㩿Ʀ㪫㪈㪂Ʀ㪫㪉㪀㪆㪉×㪈㪅㪈
Diagnosis point

Related product manuals