6-4. Air conditioner operates, but abnormalities are observed.
6-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT).
•
Indoor PCB Ass'y is defective.
•
Check voltage between terminals
No. 1(+) and No. 4 at the terminal
plate. (AC 220–240V)
No voltage appears.
•
Remote control unit may be defective.
•
Measure resistance of 4–way valve's
winding.
Receiver in lamp Ass'y may be
defective.
COOL ➞ HEAT
•
Check voltage between terminals
No. 1(+) and No. 4 at the terminal
plate. (0V)
HEAT ➞ COOL