22
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
Indoor Unit SAPK241GJA
SAPK241GJA
SAPK241MBA
SAPK241MBA
Outdoor Unit SAPC241GA
SAPC241JA
SAPC241MA
SAPC241BA
Compressor
Wide tube
service
valve
Wide tube
O.D.
ø15.88 mm
(5/8 ")
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Evaporator
Capillary for
liquid injection
Indoor Unit Outdoor Unit
Muffler
Capillary tube
Condenser
Strainer
Accumulator