33
6. ELECTRICAL DATA
6-1. Electrical Characteristics
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.40 0.54 7.17 8.1
Power Input kW 0.079 0.119 1.572 1.77
Full Load Conditions Running Amps. A 0.40 0.54 8.87 9.8
Power Input kW 0.079 0.119 1.942 2.14
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAP–K161GJA
Outdoor Unit SAP–C161JA
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.37 / 0.38 0.48 / 0.50 6.35 / 6.42 7.2 / 7.3
Power Input kW 0.070 / 0.073 0.105 / 0.119 1.365 / 1.418 1.54 / 1.61
Full Load Conditions Running Amps. A 0.37 / 0.38 0.48 / 0.50 8.05 / 7.82 8.9 / 8.7
Power Input kW 0.070 / 0.073 0.105 / 0.119 1.735 / 1.778 1.91 / 1.97
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit SAP–K161GJA
Outdoor Unit SAP–C161GA