Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.40 0.54 6.87 7.8
Power Input kW 0.079 0.119 1.502 1.70
SSA 385, 386 Running Amps. 0.40 0.54 8.17 9.1
Conditions Power Input 0.079 0.119 1.792 1.99
Full Load Conditions Running Amps. A 0.40 0.54 9.87 10.8
Power Input kW 0.079 0.119 2.162 2.36
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
SSA 385, 386 Conditions (Saudi standard)
: Indoor Air Temperature 29°C D.B. / 19°C W.B.
Outdoor Air Temperature 46°C D.B. / 24°C W.B.
Full Load Conditions : Indoor Air Temperature 29°C D.B. / 19°C W.B.
Outdoor Air Temperature 54°C D.B.
Indoor Unit SAP–K181GJA SAP–K181MBA
Outdoor Unit SAP–C181JA SAP–C181BA
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at
Rating Conditions Running Amps. A 0.37 / 0.38 0.48 / 0.50 8.75 / 8.62 9.6 / 9.5
Power Input kW 0.070 / 0.073 0.105 / 0.119 1.855 / 1.918 2.03 / 2.11
Full Load Conditions Running Amps. A 0.37 / 0.38 0.48 / 0.50 13.05 / 12.52 13.9 / 13.4
Power Input kW 0.070 / 0.073 0.105 / 0.119 2.785 / 2.838 2.96 / 3.03
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 52°C D.B.
Indoor Unit SAP–K181GJA SAP–K181MBA
Outdoor Unit SAP–C181GA SAP–C181MA