8-4. Freeze Prevention (Cooling and Dry)
This function prevents freezing of the indoor heat exchange coil.
When the compressor has been running for 6 minutes or more and the temperature of the indoor heat exchange
coil falls below –0.8°C, the control circuit stops the compressor for at least 6 minutes. The compressor does not
start again until the temperature rises above 8°C or 6 minutes has elapsed.
8-5. Compressor Overcurrent Protection (Cooling, Dry and Heating)
This function prevents the compressor from being damaged by overcurrent.
When the compressor current exceeds either H1(A) for 2 seconds or H2(A) for 8 seconds, both compressor
and outdoor fan stop (Trip). At the same time, operation lamp in front of the indoor unit flashes.
After 3 minutes, this function automatically releases and resumes operation until tripping repeats 8 times.
If the tripping repeats 9 times or more, the unit stops its operation.
The operation temperature shown as H1 and H2 in the chart above differ by models.
NOTE
2 sec.
Tr ip
Tr ip
Tr ip
7 sec.8 sec.6 sec.
About
H1 (A)
About
H2 (A)
1 sec.
Compressor
current (A)
30
SAP-K92AH SAP-K122AH
H1 16 22
H2 7 10