ECO MULTI SYSTEM Unit Spesifications
SM830052
I-4
1
1. Outdoor Unit
MODEL No. Outdoor Unit SPW – C483GY8
POWER SOURCE 380 - 400 - 415 V / 3 phase / 50Hz
PERFORMANCE Cooling
Capacity kW 14
BTU / h 47,800
Air circulation (Hi) m
3
/min(cu. ft/min) 84 (2,970)
ELECTRICAL RATINGS
Voltage rating V 380 - 400 - 415
Available voltage range V 342 - 456
Running amperes A 8.5 - 8.5 - 8.8
Max. running amperes* A 10.0 - 9.9 - 10.0
Power input kW 4.87 - 4.92 - 4.97
Max. power input* kW 5.90 - 5.91 - 5.96
Power factor % 87 - 84 - 79
C.O.P W/W 2.87 - 2.85 - 2.82
Compressor locked rotor amperes A 62 - 65 - 67
FEATURES
Controls Microprocessor
Defrost control Reverse cycle, microprocessor control
Service function Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment kg R22 - 3.0
Refrigerant control Electronic Refrigerant Control Valve
Operation sound (Hi) dB-A 55
REFRIGERANT TUBING
Limit of tubing length m(ft.) 50 (164)
Limit of elevation difference m(ft.) Outdoor unit is higher than indoor unit : 40 (131)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in) 9.52 ( 3 / 8 )
outer diameter Wide tube mm (in) 19.05 ( 3 / 4 )
Refrigerant tubing kit / joint kit Optional
DIMENSIONS & WEIGHT Unit dimensions Package dimensions
Unit dimensions Height mm(in) 1,235 (48 - 20/32) 1,326 (52 - 7 /32)
Width mm(in) 940 (37 ) 1,016 (40 )
Depth mm(in) 340 (13 - 12 /32) 416 (16 - 12 /32)
Net weight kg(lb) 107 ( 236 )
Shipping weight kg(lb) 114 ( 251 )
Shipping volume m
3
(Cu. ft.) 0.56 ( 19.8 )
Unit specifications (B)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27 °C DB / 19.0 °C WB , Outdoor air temperature 35 °C DB
* Full load conditions at Indoor / outdoor capacity ratio 100 %
Cooling: Indoor air temperature 32 °C DB / 22.5 °C WB , Outdoor air temperature 43 °C DB / 25.5 °C WB