II - 8
Processes and Functions
SM830052
2
8. Automatic Cooling Control
Valid only for connection of one indoor unit (or one group).
Cooling and heating operations are selected automatically so that the room temperature is equal to set temperature
plus shift temperature.
(1) At the start of operation, the mode is determined by the body sensor and the remote control temperature setting.
Body sensor temperature ] remote control temperature setting cooling operation
Body sensor temperature < remote control temperature setting heating operation
(2) Then, operation is controlled so that the room temperature is the temperature below (Tsc, Tsh).
Cooling mode Tsc = remote control temperature setting + [2.0] *
Heating mode Tsh = remote control temperature setting – [2.0] *
* The values in brackets are the factory settings. These values can be set within the range of 0 to 10 ˚C with the
remote controller detailed setting mode.
(3) Operation mode change
In cooling mode, when room temperature falls below [Tsc – 1.0] ˚C
changes to heating mode
In heating mode, when room temperature rises above [Tsh + 0.5] ˚C
changes to cooling mode
The mode does not change during the first 10 minutes after the start of operation.
9. Dehumidifying Control
0320_M_
I
: Heating mode
Remote control
temperature
setting
+2.5
–3.0
Tsc + [2.0]
Tsh – [2.0]
: Cooling mode
Operation time
0321_M_I
Room
temperature
(°C)
A
A: Normal cooling operation
B: Thermostat on • • • • •
Thermostat off • • • • •
L
LL
: Low fan speed
: Very low fan speed
B
Remote control
temperature setting
+1