ECO MULTI SYSTEM Unit Spesifications
SM830052
I-14
1
Other component specifications
1. Outdoor Unit
MODEL No. Outdoor Unit
SPW – C703GYH8 / SPW – C703GY8
SPW – C903GYH8 / SPW – C903GY8
Power Transformer ATR-II45, CT CL-3
Thermostat
Available
Cooling 18 – 30 °C
(Option) setting temp.
Dry 18 – 30 °C
Heating 16 – 26 °C
Thermistor (Coil sensor) PBC-41E-S36
Coil resistance K –10 ˚C : 23.7 ± 5 % , 20 ˚C : 6.5 ± 5 %
–5 ˚C : 18.8 ± 5 % , 30 ˚C : 4.4 ± 5 %
0 ˚C : 15.0 ± 5 % , 40 ˚C : 3.1 ± 5 %
5 ˚C : 12.1 ± 5 % , 45 ˚C : 2.6 ± 5 %
10 ˚C : 9.7 ± 5 %
Thermistor (Discharge gas sensor
PTC-51H
or coil sensor)
Coil resistance K 60 ˚C : 13.8 ± 5 % , 90 ˚C : 5.1 ± 5 %
70 ˚C : 9.7 ± 5 % , 100 ˚C : 3.8 ± 5 %
75 ˚C : 8.2 ± 5 % , 110 ˚C : 2.8 ± 5 %
80 ˚C : 7.0 ± 5 % , 120 ˚C : 2.2 ± 5 %
85 ˚C : 5.9 ± 5 % , 130 ˚C : 1.7 ± 5 %
Relay HH62S / 085
Coil rated V AC 220 V - 240 V
Contact rating V.A AC 250 V, 5 A
Coil Resistance (at 25 ˚C) k 17.2 ± 10 %
Solenoid control valve or coil
Solenoid control valve NEV603DXFa19 / NEV202DXFa19
Solenoid coil NEV-MOAJ504B0
Reversing valve or coil (only heat pump type)
Reversing valve VH 60100
Solenoid coil LB 60012