IV - 137
TD831077
4
W-ECO MULTI SYSTEM Unit Specifications
External Static Pressure (mmAq)
0845_V_I
Air Flow (m
3
/minute)
0
1
2
3
15 20
(Pa)
10
20
Limit line
H
M
L
External Static Pressure (mmAq)
0844_V_I
Air Flow (m
3
/minute)
0
1
2
3
10 15
(Pa)
10
20
Limit line
H
M
L
External Static Pressure (mmAq)
0843_V_I
Air Flow (m
3
/minute)
0
1
2
3
510
(Pa)
10
20
Limit line
H
M
L
External Static Pressure (mmAq)
0842_V_I
Air Flow (m
3
/minute)
0
1
2
3
510
(Pa)
10
20
Limit line
H
M
L
10. Concealed Floor-Standing Type (FM Type)
10-6. Indoor fan performance
How to Read the Diagram
The vertical axis is the EXTERNAL STATIC PRESSURE (mmAq) while the horizontal axis represents the AIR
FLOW (m
3
/minute). The characteristic curve for the “H”, “Med”, and “Lo” fan speed control.
The name plate values are shown based on the “H” air flow. Therefore in the case of the 25 type the flow is 17 m
3
/
minute, while the EXTERNAL STATIC PRESSURE is 1.5 mmAq at “H” position. If the external static pressure is too
great (due to long extention of duct, for example), the air flow volume may drop too low at each air outlet.
12 Type
25 Type
9 Type
18 Type

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo SPW-CR1903GDYH8 and is the answer not in the manual?

Sanyo SPW-CR1903GDYH8 Specifications

General IconGeneral
BrandSanyo
ModelSPW-CR1903GDYH8
CategoryAir Conditioner
LanguageEnglish

Related product manuals