36 S4179705
7. Electrical Wiring
7-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the
wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and
circuit breaker for overcurrent protection should
be provided in the exclusive line.
(3) To prevent possible hazards from insulation
failure, the unit must be grounded.
(4) Each wiring connection must be done in accor-
dance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or
become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can
be very dangerous. The manufacturer will accept
no responsibility for any damage or misoperation
that occurs as a result of such unauthorized
changes.
(7) Regulations on wire diameters differ from locality
to locality. For field wiring rules, please refer to
your LOCAL ELECTRICAL CODES before
beginning. You must ensure that installation
complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner
caused by electrical noise, care must be taken
when wiring as follows:
The inter-unit control wiring and the wired remote
control wiring (option) should be wired apart from
the inter-unit power wiring.
It is recommended that shielding wires or twisted
pair wires be used for the wired remote control
(option) and the inter-unit control wiring if the air
conditioner is installed where it is exposed to the
influence of electrical and/or electro-magnetic
noise.
7-2. Recommended Wire Length and Wire Diameter for Power Supply System
Models (A)
*1
Power Supply (B)
*1
Inter-unit (C)
*1
Inter-unit Time Delay Fuse Power Supply Terminal Base (Outdoor Unit)
Wiring Control Wiring or Circuit Capacity Capacity Max. Wire Diameter
XHS2432 CH2432
AWG #12
*2
AWG #14
*2
AWG #18
30A 50A AWG #6
*2
69 ft. 165 ft. Max. 3,000 ft.
KHS2432
CH2432
AWG #10
*2
AWG #10
*2
AWG #18
35A 50A AWG #6
*2
THS2432
76 ft. 165 ft. Max. 3,000 ft.
XHS3632
CH3632
AWG #10
*2
AWG #14
*2
AWG #18
35A 50A AWG #6
*2
KHS3632
86 ft. 165 ft. Max. 3,000 ft.
THS3632 CH3632
AWG #8
*2
AWG #8
*2
AWG #18
45A 50A AWG #6
*2
88 ft. 165 ft. Max. 3,000 ft.
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of A, B.
AWG = American Wire Gauge
*2 Wires connected to terminal base shall be provided with a ring pressure terminal securely fastened in place.
NOTE
To access the electrical component box, turn off the
power supply, then open the air intake grille and
remove the electrical component box cover.
1) Inter-Unit Control Wiring (c) has no polarity.
But for other wiring, respect polarity.
Be sure to connect as shown in the Wiring Sys-
tem Diagram.
2) The basic connection diagram of the indoor unit
shows the 5P terminal board.
Fig. 7-1
12
Power
supply
U1
Inter-unit
control wiring
U2
5P terminal board
1104_M_I
THS
Inter-unit
control wiring
4P terminal board
1105_M_I
12
Power
supply
U1 U2
KHS, XHS