SATEL PK-01 5
[7#] Program relay operation time
[8#] Configure relay operation time reducing function:
[0#] disabled
[1#] when door open
[2#] when door closed
[9#] Configure backlighting:
[0#] off
[1#] automatic
[2#] permanent
When navigating through the service mode, keep the following principles in mind:
1. After selecting a function from the main menu (from 1 to 9), the green and red LEDs will
be steadily lit.
2. After saving each change, the module will generate 4 four short beeps and 1 long beep.
The entry of erroneous data is indicated with 2 long beeps. In both cases, after generating
the signal, the device returns to the main menu.
3. To exit the function, without making or confirming any change, press the key.
Exiting the service mode
Press the key and confirm with the key. The module will generate 4 short beeps and 1
long beep.
Adding / editing the user code
Notes:
Adding a new code is equivalent to adding a user.
You can enter up to 49 user codes.
You cannot delete the administrator.
During the process of adding codes, it is recommended that you additionally make a list of
users and numbers assigned to them.
1. Press the key and confirm with the key. The module will generate 2 short beeps.
2. Enter the number of user to whom a code is to be added / whose code is to be changed.
Note: If the yellow LED lights up after entering the user number, it means that the code of a
user with this number is already saved in the module.
3. Confirm with the key. The module will generate 2 short beeps.
4. Enter the code.
Note: If the entered code has already been assigned to another user, the module will
generate 2 long beeps. In such a case the whole procedure of code adding should be
repeated from the beginning.
5. Confirm with the key. The module will generate 4 short beeps and 1 long beep.
Deleting the user code
1. Press the key and confirm with the key. The module will generate 2 short beeps.
2. Enter the number of the user whose code is to be removed.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Satel PK-01 and is the answer not in the manual?

Satel PK-01 Specifications

Power IconPower
supply voltage12 V DC ±15%
standby current consumption105 mA
maximum current consumption125 mA
Operating Environment IconOperating Environment
maximum humidity93±3%
operating temperature range-25 to +55 °C
environmental class according to EN50130-5III
Output Ratings IconOutput Ratings
bell output rating30 mA
alarm output rating30 mA
relay contacts rating (resistive load)2 A / 24 V DC
Frequency IconFrequency
reader working frequency125 kHz
Weight and Dimensions IconWeight and Dimensions
weight297 g
enclosure dimensions47 x 158 x 24 mm