Operator's Manual: Models Saturn™ 140 & Saturn™ 230
4-3
Selecting a Location
Guidelines for Selecting a Location
The location you select for your furnace must allow the following:
Unobstructed, even heat distribution.
Safe, easy access for servicing.
Unobstructed passage for shop vehicles and equipment.
Proper clearances from combustibles. Verify according to your local safety codes.
Adequate combustion air per local codes.
Proper stack installation.
WARNING: Adhere to the following minimum clearances from combustible surfaces and
to provide adequate clearance for servicing (also refer to Figure 4B for visual reference); failure to
maintain proper clearances may result in fire, explosion, personal injury or death.
WARNING: Codes may require
that your furnace is mounted a
minimum of eight (8) feet off the ground when
installing the furnace in a repair facility. Refer to
NFPA-88B, Standard for Repair Garages,
Chapter 3, Hazards, Sec. 3-2.3.1.
CLEARANCES FOR INSTALLATION
TOP (of furnace)............................... 12"
FRONT (burner) ............................... 48"
SIDE (with or without stack)............. 12"
CHIMNEY CONNECTOR ................. 18"
REAR ..... .............................. .... 12"
BOTTOM (with air diffuser) ............... 30"
BOTTOM (without air diffuser) .......... 60"
Figure 4B - Clearances from Combustibles
NOTE: See Appendix A for furnace cabinet dimensions.