APPENDIX A
Detailed Furnace Specifications
* Nominal values; actual values may vary depending on installation.
Furnace Model
Saturn
TM
140
Saturn
TM
230
BTUH Input
140,000*
@ 1.0 GPH
230,000*
@ 1.6 GPH
Listed Fuels:
#2 Fuel Oil
#4 and #5 Fuel Oils (U.S.)
Used Crankcase Oil
Used ATF (U.S.)
Used Hydraulic Oil
#2 Fuel Oil
#4 and #5 Fuel Oils (U.S.)
Used Crankcase Oil
Used ATF (U.S.)
Used Hydraulic Oil
Cabinet Dimensions
(LxWxH) inches
47.25 x 32 x 20
54.5 x 35 x 23
Furnace Dimensions
w/ fan, Burner, and Louvers
(LxWxH) inches
61.25 x 32 x 31.5
68.5 x 35 x 34.5
Approximate Weight
(complete furnace system – uncrated)
220 lbs.
280 lbs.
Mounting (NFPA-31)
1) Ceiling hung
2) Raised platform
3) Bench Tank Kit
1) Ceiling hung
2) Raised platform
3) Bench Tank Kit
Electrical Requirements
(VAC @ 60 Hz)
115
115
Circuit Breaker
20 amps
20 amps
Wall Thermostat
24 volt
24 volt
Oil Pump
Suntec
A2RA-7720
Suntec
A2RA-7720
Oil Pump Motor
Bison Gear Motor
1/20 HP
Bison Gear Motor
1/20 HP
Pump Motor Rotation
CCW shaft end
CCW shaft end
Canister Filter
Lenz
DH 750-100
Lenz
DH 750-100
Stack Size
6”
6”
Fan Motor HP
1
/
4
HP
1
/
3
HP
Blower/Fan Switch
F180
F180
Hi-Temp Limit Switch
L200
L200
Auxiliary Hi-Temp Switch
L290 (Auto-Reset)
L290 (Auto-Reset)
Approx. Air Compressor
Requirements
2.5 CFM
@ 30 PSI
2.5 CFM
@ 30 PSI