STEUEREINHEIT AIRBASIC 2 –GEBRAUCHSANWEISUNGEN
AIRBASIC 2 CONTROLLER – USER MANUAL
43
P18 - Max restarts per hour
Defines the maximum number of permitted start-ups per hour. Its purpose is to protect the motor from
damage. When the set number of restarts is reached, the motor will not stop for the rest of the following
hour and the compressor will work without interruption, switching from load to unload and vice versa.
This condition is identified by the simultaneous flashing of LEDs x10, x100 and ( / ).
At the end of the hour period, the counter is reset and the motor will be able to stop at the end of a unload
phase.
P19 - Air filter maintenance pre-alarm hours
Defines the air filter change countdown timer value.
When the set timer has elapsed, the controller will warn the operator that maintenance is needed by
showing a dedicated warning message (S02) on the display.
P20 - Oil filter maintenance pre-alarm hours
Defines the oil filter change countdown timer value.
When the set timer has elapsed, the controller will warn the operator that maintenance is needed by
showing a dedicated warning message (S03) on the display.
P21 - Separator filter maintenance pre-alarm hours
Defines the separator filter change countdown timer value.
When the set timer has elapsed, the controller will warn the operator that maintenance is needed by
showing a dedicated warning message (S04) on the display.
P22 - Oil maintenance pre-alarm hours
Defines the oil change countdown timer value.
When the set timer has elapsed, the controller will warn the operator that maintenance is needed by
showing a dedicated warning message (S01) on the display.
P23 - Overall maintenance pre-alarm hours
Defines the general maintenance countdown timer value.
When the set timer has elapsed, the controller will warn the operator that maintenance is needed by
showing a dedicated warning message (S06) on the display.
P24 – Measurement unit for pressure
This parameter permits to select the measurement unit for the pressure
P24=0 pressure in bar
P24=1 pressure in psi
P25 – Measurement unit for temperature
This parameter permits to select the measurement unit for the temperature
P25=0 temperature in Celsius degree °C
P25=1 temperature in Fahrenheit degree °F