STEUEREINHEIT AIRBASIC 2 –GEBRAUCHSANWEISUNGEN
AIRBASIC 2 CONTROLLER – USER MANUAL
45
P29 – Input IN5 function
Defines the possibility to program an auxiliary input:
P29=0 is not used
P29=1 with open contact occurs a pre-alarm with a message a06 on the display
P29=2 with open contact occurs an alarm with a message A06 on the display
P30 – Profile selection
The contoller has two lists of default parameters :
P30=0 select the values of default profile 0
P30=1 select the values of default profile 1
P31 – Compressor address
For each compressor is possible to assign an address from 1 to 30. This address is used to identify a
compressor if a communication in MODBUS, through the RS232 serial port, is activated.
P32 – Input load/unload remote function enable
The input for the remote load/unload contact can be enabled or disable
P32=0 input disabled
P32=1 input enabled