3. Preparation before use
3.1. Positioning the generating set for operation
Choose a site that is clean, well ventilated and sheltered from bad weather.
Place the generating set on a flat, horizontal surface which is firm enough to prevent the set sinking down (under no circumstances
should the set tilt in any direction by more than 10°).
Store the additional supplies of oil and fuel within close proximity, whilst maintaining a certain distance for safety.
3.2. Earthing the generating set
Danger
The generating sets supply electrical current when in operation: risk of electrocution.
Connect the generating set to the ground at each use.
To connect the set to the ground: Attach a 10 mm
2
copper wire to the set’s earth connection and to a galvanised steel earthing rod
driven 1 meter into the ground.
3.3. Checking the oil level
Attention
Before starting–up the generating set, always check the engine oil level.
Make sure the recommended oil is used (see § Specifications) and use a funnel to fill-up to the maximum limit
indicated on the dipstick.
Allow the generating set to cool down for at least 30 minutes before checking the oil level.
n Retract the oil-level dipstick (fig. B - mark 1) and wipe it.
o Replace the oil-level dipstick and pull it out again.
p Check the level visually. It should be within the upper limit shown on the dipstick (fig. B – mark 2) and the lower limit on the dipstick
(fig. B - mark 3). Correct as required.
q Replace the dipstick.
r Check that there are no leaks.
s Wipe off excess oil with a clean cloth.
3.4. Checking the fuel level
Danger
Filling with fuel must be carried out when the engine is switched off and as per the safety
instructions (see § Filling with fuel).
Check the fuel level on the fuel gauge (fig. A - mark 3). If necessary, fill-up:
n Unscrew the fuel tank filler cap (fig. A - mark 4).
o Fill the tank until the fuel gauge shows "F ", using the funnel and taking care not to spill any fuel.
Attention
Only use clean fuel without any water.
Do not overfill the tank (there should not be any fuel in the filler neck).
After filling-up, always check that the fuel tank filler cap is tightly closed.
If any fuel has been spilled, make sure that it has dried out and that any associated fumes have dissolved in the
atmosphere before starting-up the generator set.
p Screw down the fuel tank filler cap tightly.
3.5. Checking the starter battery
Danger
Never place the battery close to a flame or fire.
Use only insulated tools.
Never use sulphuric acid or acid water to top up the electrolyte level.
n Ensure that the battery (no. 16, diag. A) "-" terminal is connected to the circuit correctly.
4. Using the generator set
Warning
Before use:
- make sure you know how to stop the generating set in the event of an emergency,
- make sure you completely understand all the controls and operations.
To stop the generating set urgently, place the engine switch on "OFF" or "О".