APPENDIX B CARD ACCESS INPUT MODE
The Card Access Input Mode is ONLY Available for the SMT Advantage 500DE with Secure Care Part Number
A05160911 and SMT Advantage 1000DE with Secure Care Part Number A10000908. Both will have a label that
says APM on the front of the panel.
The Card Access Mode is used with Card Access Systems that want to integrate with the SMT Advantage 500DE panels.
To install the Card Access with the exit panel, two conductors from the Card Readers NORMALLY OPEN AND
COMMON DRY CONTACT outputs are wired into the two conductors on the ribbon cable closest to the programming
port on the exit panel. The ribbon cable is shipped in a two foot length with seven pin connectors on both ends. Cut the
ribbon cable to the desired length stripping two of the end conductors back. The ribbon cable then needs to be placed on
the seven pins on the exit panel with the two conductors being used closest to the programming port on the exit panel.
WARNING: USE ONLY THE TWO CONDUCTORS SPECIFIED ON THE SEVEN PIN RIBBON
CABLE AND NOT ANY OF THE OTHER CONDUCTORS OR DAMAGE TO THE PANEL MAY
OCCUR.
NO VOLTAGE IS TO BE APPLIED TO THE TWO PINS USED FOR THE CARD ACCESS INPUT
MODE.
Using the Card Access with the SMT Advantage 500DE panels
With the Card Access System connected to the SMT Advantage 500DE you can escort a resident through the locked door
by swiping your access card once. If there is an alarm at the SMT Advantage 500DE then you can clear the alarm by
swiping once with your access card. When you need to escort a resident and there is an alarm at the door then you need to
swipe twice, one to clear the alarm and on
PROGRAMMING
PORT
THE ONLY TWO CONDUCTORS
THAT ARE USED FOR CARD ACESS
INPUT MODE
12 VDC
- +
EGRESS
DOOR PUSH FIRE
PROGRAMMING
PORT
RECHARGEABLE 9V NI-MH
BATTERY ONLY
EXTERNAL KEYPAD
ON / OFF
MUTE
HI / LO
ELEV
NURSE
LOCK
LOCK
NO C NC
NO C NC
NO C NC
NO C NC
A05032031 2 FOOT SEVEN PIN
RIBBON CABLE