Section 15 -Data Field Descriptions
15–5
47 PHONE SYSTEM SELECT 3
If Central Station is NOT on a WATS line: 0 = Pulse dial, 1 = Tone dial
If Central Station IS on a WATS line: 2 = Pulse dial, 3 = Tone dial
48 REPORT FORMAT
7 | 7
0
= 3+1, 4+1
Ademco LOW SPEED STANDARD
Prim Sec
1
= 3+1, 4+1
RADIONICS STANDARD
2
= 4+2
Ademco LOW SPEED STANDARD
3
= 4+2
RADIONICS STANDARD
6 or undefined
= 4+2
Ademco EXPRESS
7
=
Ademco CONTACT ID REPORTING
8
= 3+1. 4+1
Ademco LOW SPEED EXPANDED
9
= 3+1. 4+1
RADIONICS EXPANDED
49 SPLIT/DUAL REPORTING 0
0 = Disable (Backup report only)
Use
options
1 - 5 when reporting to standard telephone receivers:
To
Primary Phone No.
To Secondary Phone No.
1 =
Alarms, Restore, Cancel
Others
2 =
All except Open/Close, Test
Open/Close, Test
3 =
Alarms, Restore, Cancel
All
4 =
All except Open/Close, Test
All
5 =
All reports
All
50 15-SECOND DIALER DELAY (BURG) 1
0 = No delay; 1 = Yes. Must be “0” for UL installations.
Above options (1 through 5) provide delay of
BURGLARY ALARM
and
FIRE ALARM
reporting (except zone type 24) to the Central Station, which
allows time for the subscriber to avoid a false alarm transmission. This delay
does not apply to zone type 24 alarms (silent type), which are always sent as
soon as they occur.
UL installations: Must be set to 0 (no delay).
51 PERIODIC TEST REPORT 0
0 = no test report
1 = once every 24 hours
2 = weekly
3 = once every 30 days
Test Report Code entered in field
64 is sent. Reports with Subscriber No.
52 TEST REPORT OFFSET 2
0 = 24 hours after exiting Program mode or download
1 = 6 hours after exiting Program mode or download
2 = 12 hours after exiting Program mode or download
3 = 18 hours after exiting Program mode or download
This is the time to first report from Programming mode or downloading.