5.2 Default Settings
All WIC1 relay versions are set in our works at the smallest possible setting values.
Is = smallest possible rated current (W1=8, W2=16A, W3=32A, W4=64A, W5=128A, W6=256A)
Characteristic: Definite Time
I> = 0.9 x In
tI> = 0.04s
I>> = 1.00 x In
tI>> = 0.04s
IE> = 0.20 x IN
tIE> = 0.10s