SEG Electronics GmbH Technical Manual WIC1
24 DOK-TD-WIC1E, Rev. M
5.3 Routine safety check
In case of misadjustment of the relay, e.g. selection of non-assigned switch positions, the relay operates with the
following setting values.
I
S
= upper rated CT current
Characteristic = DEFT
I> = Deactivated (Exit)
t
I>
= 0.04 s
I>> = 20 x I
S
t
I>>
= 0.04 s
With earth fault element
I
E>
= 2.5 x I
S
t
IE>
= 0.1 s
A circuitry is integrated to give an additional back-up protection in case of processor or storage errors. By this cir-
cuitry a short-circuit protection with the following trip values is guaranteed:
I>> = 20 times highest rated CT current
tI>> = 40 ms
The relay option WIC1-xxx-W works with an additional backup-protection when
The watch-dog of the microcontroller responded,
0.8 times lowest rated CT current is flowing,
the energy storage is charged (charging time is 1s at lower rated CT current),
5.4 Fault value memory
A fault value memory is integrated in the WIC1 where data of the latest fault occurrence is stored. The stored in-
formation can only be read out via the PC interface. The following fault references are available:
the protective element causing the trip or an externally triggered trip
values of the trip current in the individual phases or earth fault currents (with E type)