MI00035 -E9 ENGLISH - 2/8
INSTALLATION RULES
The Z111 modules have been designed for mounting on DIN 46277 guides in vertical
position.
For long-lasting and optimum working life, the module(s) must be ensured adequate
ventilation. Make sure to position the cable raceways and any other objects in such
way as to avoid clogging the ventilation slots.
Also avoid positioning the modules above equipment that generates heat. For this
reason, we recommend performing installation in the lower part of the panel.
TAXING WORK CONDITIONS:
The following are considered taxing work conditions:
elevated power supply voltage (> 30V DC / > 26 V AC)
providing power supply to sensor input.
use of the active current output.
When paired modules are installed, in they may require separation by at least 5 mm
the following cases:
With panel temperatures of more than 45°C in concomitance with at least one of the
taxing work conditions above.
With panel temperatures of more than 35°C in concomitance with at least two of the
taxing work conditions above.