24
8.2 MAINTENANCE UPDATE
SC_2VX






 
The icone 
Once the maintenance has been done, enter a new frequency setting (see
6.2.3Navigatingthemenu
): the
new maintenance date is set and the icon disappears.
9. FAULT FINDING
Alarm message on the dis-
play
Possible cause Remedy
No AC No power supply.
Check power supply.
Turn the current switch into position ON (I)
Pump P1 switched OFF
Pump 1 deactivated
(activation lamp lights up red).
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Pump P2 switched OFF
Pump 2 deactivated
(activation lamp lights up red).
Reactivate the pump by pressing the activation button.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
No pump activated
Pumps deactivated
(activation lamps light up red).
Reactivate the pumps by pressing the activation buttons.
In case of automatic deactivation, check the alarm log to verify
the cause of the problem.
Levels sensors fault
Clogged sensor
Clean the sensor, unclog the compression chambers.
Remove deposits in the tank.
Blocked sensor
Check that the oats move freely.
Remove deposits in the tank.
Incorrect wiring of the sensors. Check the wiring of the sensor terminals.
Incorrect connection of the sensors. Check the correct location of the oat connection on the casing.
Incorrect position of the oats on the rail. Check the position of the oats.
Float defective. Contact after-sales service.
P1 I=0 Amp
P2 I=0 Amp
Pump disconnected.
Check pump connection.
Check the wiring of the pump terminals.
Thermal break.
Pump connection occurs automatically after a delay.
Thermal break is a symptom of a malfunction that requires a
thorough check.
Defective pump. Check the pump.
P1 hydraulic issue
P2 hydraulic issue
Problem pump cover plate.
Impeller problem.
Check pump hydraulics.
Clogged pipe. Check the discharge pipe.
Shut-o valve closed Open the shut-o valve
P1 I>Imax
P2 I>Imax
Blockage of the pump. Check for foreign bodies
Motor failure Contact after-sales service.
Evacuation issue
Unable to evacuate water from the
station.
Check for clogged discharge pipe.
Check that the shut-o valve is open.
Check that both pumps are working properly.
10. FOR PROFESSIONALS
10.1 RETURN TO THE START-UP SCREEN
You can return to the settings made when the device was commis-
sioned by pressing the 4 arrow keys , , and .
In particular, the choice of the connected station can be changed.
10.2 EXPLANATION OF THE LEDS ON THE ELECTRONIC
BOARD
ALARM BOX
LOOP P2
CCMOS
CONNECT COM
IOT CABLE ONLY
BMS2 RM BMS1 NC BMS1 NO
FLOOD SENSOR
N / C / L
N / C / L
LOOP P1
AC POWER
SCREENBOARD
N / L
CLR CMOS
OFF/ALARM/ON
BMS2
BMS1 NO
BMS1 NC
Green LED
Pumps
Red LED
BMS
Blue LED
Sensors
Note: The pho-
tograph below
is used as an
example. In-
deed, the lo-
cation of the
LEDs may vary
but the col-
ours and their
indications are
identical to
all electronic
boards.








NOTICE
If the enclosure has been opened, take care not to
pinch or pull the cable when refitting the front panel.
10.3 LEARNING LOOPS
The management of the delay time in Automatic” mode is not ad-
justable. It is calculated using a learning loop that averages the last 5
switch-ons.
An increasing delay time is the symptom of a drop in output ow and
may therefore indicate a fault in the discharge installation (clogging, etc.).
11. GUARANTEE
Smart Control Box is guaranteed for 2 years for parts and labour, sub-
ject to correct installation, use and maintenance of the unit.