Symptom Check Defect Remedy
Compressor operates
in cooling but fan
doesn't rotate
2) Check fan capacitor
1) Connector open CN1
1) Joint of connector CN1
Noise
Excessive vibration
and noise
Capacitor defective
1) Insulation unstable
Piping touches cabinet or other parts
2) Screw or nut loose causing
vibrating noise
2) Electric parts
4) Cabinet or parts set-screws
loosened
5) Fan touching
Change capacitor
Change fan motor
1) Secure
2) Secure
Replace
2) Repair or change
4) Tighten up
6) Secure
2) Cabinet screw loose
2) Tighten up
2) Metallic sound
1) Compressor
3) Piping touched
6) Insulation unstable
3) Repair
1) Change compressor
1) Fan cracked or deformed
Repair
1) Change fan
1) Check PWB
connector CN1
1) Vibrating noise
3) Noise created by
fan
Compressor mounts defective
Check noise source
3) Check fan motor
5) Adjust
Fan motor defective
Check mounting of
compressor
Symptom Check Defect Remedy
PWB ass'y does not 
operate
2) Check transformer
(TR)
1) Fuse(FU1)open
1) Change fuse(FU1)(NR)
The room is not cool 
enough or not cool 
at all.
The compressor 
does not turn off
2) Secondary voltage of 
transformer (TR)
Check thermistor 
(Refer to page 27)
2) Change PWB ass'y
Change thermistor
Defective compressor relay
Change relay or 
Replace PWB ass'y
1) Check fuse(FU1)
Check thermistor
Check compressor 
relay
Control circuit
2) Crack at solder part of CN1 2) Over solder