ESA ESTRO - E7014P rev. 02 - 03/05/17
www.esapyronics.com
4
CHARACTERISTICS
INPUTS AND OUTPUTS:
¾
¾Voltage to the flame detection probe: max 300 Vac
¾
¾Minimum ionization current: 2,4 µA ± 0,3 µA
¾
¾Current limits to the probe: 1 mA
¾
¾Flame signal display: 0 ÷ 90 µA
¾
¾Detection probe type: electrode or scanner ESA UV-2
¾
¾Probe line length to electrode or UV-2 detection: < 30 m
¾
¾Insulation between the probe conductors: > 50 M (cables with double insulation or double protection)
¾
¾HV
cable length from ignition transformer: maximum 2 m
¾
¾Distance between ignition electrode and burner mass: 3 mm ± 0,5
¾
¾Digital input voltage: the same as the supply voltage
¾
¾Digital input absorption: max 5mA
¾
¾Filter for digital input: RC 100 - 0,47 µF - 250 Vac
¾
¾Output voltage: the same as the supply voltage
¾
¾Maximum current per single output: 1,5 A (2 A for ignition transformer)
¾
¾Total maximum current for all outputs: 3.15A per 10 second / minute
¾
¾Output protection fuse: 3.15A rapid (*) replaceable
¾
¾Internal relay protection fuse: 4 A not replaceable
¾
¾Instrument protection fuse: 1 A not replaceable
¾
¾Minimum voltage supply to maintain output: 70Vac (version 115Vac) and
140Vac (version 230Vac)
¾
¾EXP-2, EXP-4 and EXP5 expansion card input voltage: 24 Vac/Vdc, 115 Vac, 230 Vac
¾
¾EXP-2, EXP-4 e EXP5 expansion card input absorption: max 5mA
¾
¾EXP-2, EXP-4 e EXP5 expansion card output voltage: the same as the supply voltage
¾
¾EXP-2, EXP-4 e EXP5 expansion card output maximum current: 2A (not protected by internal fuse)
(*) On request it is possible to implement a fast fuse 4A.
PARAMETERS:
¾
¾Purging
or waiting time before ignition: 0 ÷ 99 sec or 2 ÷ 20 min
¾
¾1st gas stage safety time*: 1 ÷ 25 sec
¾
¾Regulation delay time or 2nd gas stage safety time*: 0 ÷ 25 sec
¾
¾Reaction time*: 1 ÷ 20 sec
¾
¾Shut off purging or waiting time: 0 ÷ 99 sec or 2 ÷ 4 min
¾
¾Accepted remote unlocks: max 5 in 15 minutes
¾
¾Flame sensor check on permanent operation: in 1 hour
¾
¾Auto shut down for test with non permanent operation: in 24 hours
¾
¾Behaviour at flame loss: configurable
¾
¾1st gas stage burner functioning: configurable
¾
¾Air valve functioning: configurable
* These parameters must be set according to the norm that is applicable at the time of installation.