Programming of the regeneration cycle times.
With the key Program the next phase is accessed
Programming of the litre counter divider.
This value indicates the type of litre counter divider:
0 =free litre counter divider, 1 = litre counter divider pre-programmed.
This programming acts directly on the flag 0CL.
If the free litre counter divider has been chosen, a value of between 0 and
899 impulses / litre may be set.
If the pre-programmed litre counter divider has been chosen, one of the
values suggested in tab. 24, par. 6.6 may be programmed.
Programming of the duration in minutes and seconds of the end of cycle
impulse, from 0 to 59 minutes and 59 seconds.
Divider of the dosing pump, programmable from 0 to 9999 impulses / litre.
Programming of the volume of resin in the cylinder: the value can vary
from 0 to 9999 litres.
Programming of the percentage of the total volume total of treatable water
which must be held in reserve.
Programming of the value of capacity of exchange of the resin; the value
can vary from 1.4 to 9.0.
Programming of the code of access to the programming functions. Using
the key Advance, any value from 0 to 9999 may be set.
Allows the total counter of the volume consumed to be visualised. This
cannot be modified, but only visualised. Since it is composed of 8 digits, it
is visualised in two parts;
These are the 4 higher numbers.
These are the 4 lower numbers.
Allows access to the general programming and to the setting of the flags as
already described in the previous paragraphs.
6.4 – Programming of the reserve
Aqua Timer Plus allows for the volume of water treatable to be controlled, comparing it to a possible value of reserve,
but only working in the single column modality with mixed control for the start of the regeneration. The percentage of
reserve is programmed using the code SC02 and expresses the percentage of the total volume available which must
be held in reserve. In this way, if there are 25,000 treatable litres available and 30% of reserve is required, the value
HH30 must be programmed in the code SC02 and the code SC00 must be keyed in to have the calculations on the
volume carried out. When the volume reaches the value 7,500, a regeneration which will be carried out at the
programmed time will be set.
N.B.!!
The control of the reserve is active only in the “one single column” modality with mixed control for the
regeneration.