5 Mounting
5.1 Mounting procedure
Prerequisites
Mount
ing is done in accordance with EN 50274 and electrical installation in
accordance with IEC 60204-1 in the control cabinet with enclosure rating IP54.
Mounting must be done on a non-flammable base.
Mounting is done on a 35mm mounting rail (IEC60715).
The mounting rail is connected to the functional earth.
The module is installed with a vertical orientation (on a horizontal mounting rail).
There is at least 50mm of space for air circulation above and below the module.
There is at least 25mm of space in front of the module (front side). More space
may be needed depending on the connections.
Approach
1.
Attach module to mounting rail.
Click
Figure 5: Mounting
T
he module engages with an audible click.
2. Attach the end clamps on the mounting rail on the left and right of the module.
Figure 6: Mounting the end clamps
5 MOUNTING
16
O P E R A T I N G I N S T R U C T I O N S | ReLy OSSD1 8020860/1FH0/2022-10-27 | SICK
Subject to change without notice