DC switching capacity 0.1W … 200W
see
figure 11, page 28
AC switching capacity 0.1VA … 1,500VA
Switching voltage 15VDC … 30VDC
15VA
C … 30VAC
Switching current 3mA … 100mA
Switching frequency ≤1Hz
Mechanical service life 10×10
6
s
witching operations
Contact fuse with safety fuse gG or circuit
breaker C
Max. 2A
Max. short-circuit protection ≤400A
Rated insulation voltage
At altitudes up to 2,000m above sea level 250VAC
At altitudes up to 2,000m abovesea level …
4,000m abo
ve sea level
150VAC
Overvoltage category III
Degree of contamination 2
Rated impulse withstand voltage U
im
p
6kV
Ambient data
T
able 14: Ambient data
Enclosure rating IP20 (IEC60529)
1)
Ambient operating temperature
At altitudes up to 2,000m above sea level
(UL/C
SA: surrounding air temperature)
–25°C … +55°C
At altitudes 2,000m above sea level …
3,000m abo
ve sea level
–25°C … +50°C
At altitudes 3,000m above sea level …
4,000m above sea level
–25°C … +45°C
Storage temperature –25°C … +70°C
Operating altitude Max. 4,000m above sea level
Air humidity 10% … 95%, non-condensing for climatic con‐
dit
ions according to IEC61131-2
Emitted interference According to IEC61000-6-4
Immunity to interference According to IEC61326-3-1
A
ccording to IEC61000-6-2
According to IEC60947-5-1