EasyManua.ls Logo

Siemens 3AH37 - Page 27

Siemens 3AH37
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
9229 9992 176 0D 27
2013-07-08
Position switch
Circuit-breaker tripping signal, cut-out switch (S6, S7)
S21, S22 Position switches (switch off the motor after
charging)
S3 Position switch (opens when closing spring
is charged)
S41, S42 Position switches (report charging state)
Fig. 34 Position switch (50.4.1)
The position switch S6 makes contact briefly when the
vacuum circuit-breaker is opened by means of an
electrical release.
This contacting can be used for a signal.
In the event of intentional mechanical opening, the
cut-out switch S7 interrupts the contacting.
Fig. 35 Circuit-breaker tripping signal