EasyManua.ls Logo

Siemens 3RW40 - Page 10

Siemens 3RW40
15 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 3ZX1012-0RW40-1AA1
LED displays 3RW40 Auxiliary contacts
Soft starter
Motor
protection
3RW40
DEVICE
(rd/gn)
STATE /
BYPASSED
(gn)
FAILURE
(rd)
OVERLOAD
(rd)
13 14
(ON)
13 14
(RUN)
24 23
(BYPASSED)
95 96 98
Failure /
Overload
Operating state IN_1
OFF 0
Start-up 1
Bypassed 1
Run-out 0
Warning
Ie/class setting invalid
Start-up locked,
thyristors too warm
Error
Supply voltage
electronics invalid
(U < 0.75 x Us) or
Invalid Ie/class setting and
IN (0 -> 1)
Motor protection switch-off
Thermal overload thyristors
- missing supply voltage
- phase failure
- no load voltage
Equipment error
TEST t < 2 s
TEST 2s<t<5s; Ie>0
TEST 2s<t<5s; Ie=0
TEST t > 5 s
OFF
gn green
ON
ylw yellow
flashing
rd red
flickering
English
gn
gn
gn
gn
gn
ylw
gn
gn
ylw
gn
rd
gn
rd
/
rd
gn

Related product manuals