EasyManua.ls Logo

Siemens 6MD85 - Page 108

Siemens 6MD85
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vmax threshold 10.000 kV to 340.000 kV Increments of 0.001 kV
Vmax time delay 0 s to 20 s Increments of 1 s
Blockings
V< Threshold 10.000 kV to 340.000 kV Increments of 0.001 kV
V< Time delay 0 s to 20 s Increments of 1 s
I> Threshold 10 % to 500 % Increments of 1 %
I> Time delay 0 s to 20 s Increments of 1 s
I< Threshold 3 % to 100 % Increments of 1 %
I< Time delay 0 s to 20 s Increments of 1 s
Parallel control
Parallel-transfomer id 0 to 8 Increments of 1
Maximal tap difference 1 to 9 Increments of 1
Reactive I control factor 0.01 to 100.00 Increments of 0.01
VT supervision threshold 0.5% to 10.0% Increments of 0.1 %
VT supervision time delay 1 s to 600 s Increments of 1 s
Circul. current threshold 10 % to 500 % Increments of 1 %
Circul. current time delay 0 s to 1000 s Increments of 1 s
Measured Values, Two-Winding Transformer
Measured Value Description Primary Secondary % Referenced to
V act.
Current, measured positive-
sequence voltage (referenced
to phase-to-phase)
kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act.
Voltage difference between
the target voltage and the
actual voltage
% % Voltage difference referenced
to the rated voltage of the
controlled winding
I load
Current measured load current
(positive-sequence system)
A A Load current referenced to the
rated value of the function
V max
Maximum positive-sequence
voltage ever measured (refer-
enced to phase-to-phase)
kV V Maximum voltage of the
winding referenced to the
rated voltage of the winding
V min
Minimum positive-sequence
voltage ever measured (refer-
ence to phase-to-phase)
kV V Minimum voltage of the
winding referenced to the
rated voltage of the winding
V target
Calculated target voltage with
consideration of Z compensa-
tion
kV V Target voltage of the winding
referenced to the rated voltage
of the winding
PhAng
Phase angle of the currently
measured load current
° ° -
I load Σ
Sum of the currently measured
load currents. Active when line
compensation is activated.
A A Load current referenced to the
rated current of the function
I circul.
Currently measured circulating
reactive current
A A Circulating reactive current
Vact.m
Currently measured control
voltage
kV V Current voltage of the control
referenced to the rated voltage
of the function
ΔVactV
Voltage difference % % Voltage difference referenced
to the rated voltage of the
function