Measured Value Description Primary Secondary % Referenced to
ΔVactC
Voltage difference % % Voltage difference referenced
to the rated voltage of the
function
Measured Values for Parallel Control, Proxy
Measured Value Description Primary Secondary % Referenced to
V act.
Actual voltage of winding kV V Target voltage of the primary
system referenced to the rated
voltage of the function
1/X trf.
Susceptance, internal value for
GOOSE transmission
1/Ω
I load
Load current A - Load current referenced to the
rated current of the function
PhAng
Phase angle of the load current
relative to the voltage with a
power factor of 1.0
° ° Phase angle of the load current
100 % = 180°
Measured Values, Three-Winding Transformer
Measured Value Description Primary Secondary % Referenced to
Vact.w1
Actual voltage of winding 1 kV V Target voltage of the primary
system referenced to the rated
voltage
Vact.w2
Actual voltage of winding 2 kV V Target voltage of the primary
system referenced to the rated
voltage
ΔV act.
Voltage difference between
the target voltage and the
actual voltage
% % Voltage difference referenced
to the rated voltage of the
controlled winding
I load w1
Load current of winding 1 A A Load current referenced to the
rated current of winding 1
I load w2
Load current of winding 2 A A Load current referenced to the
rated current of winding 2
Vmax 1
Maximum voltage of winding 1 kV V Maximum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmax 2
Maximum voltage of winding 2 kV V Maximum voltage of winding 2
referenced to the rated voltage
of winding 2
Vmin 1
Minimum voltage of winding 1 kV V Minimum voltage of winding 1
referenced to the rated voltage
of winding 1
Vmin 2
Minimum voltage of winding 2 kV V Minimum voltage of winding 2
referenced to the rated voltage
of winding 2
V tar.w1
Target voltage of winding 1 kV V Target voltage of winding 1
referenced to the rated voltage
of winding 1
V tar.w2
Target voltage of winding 2 kV V Target voltage of winding 2
referenced to the rated voltage
of winding 2
Technical Data
11.37 Voltage Controller
1204 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018