External Trip Initiation
Setting Values
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Approx. 10 ms + OOT
35
.
Tolerance
Sequence tolerance for delay times 1 % of the setting value or 10 ms
11.7
35
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter 11.1.4 Relay
Outputs
Technical Data
11.7 External Trip Initiation
1120 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018