EasyManua.ls Logo

Siemens 6MD86 - Page 85

Siemens 6MD86
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
f
rated
- 3.0 Hz < f < f
rated
+ 3.0 Hz ± 10 mHz at V = V
rated
df/dt, measuring window > 3 periods Approx. 3 % or 0.06 Hz/s
df/dt, measuring window ≤ 3 periods Approx. 5 % or 0.06 Hz/s
Minimum voltage 0.5 % of the setting value or 0.05 V
Minimum current 1 % of the setting value or 5 mA (I
rated
= 1 A) or 25 mA
(I
rated
= 5 A), (f
rated
± 10 %)
Power angle
Time delays 1 % of the setting value or 10 ms
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1 According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Active
Technical Data
11.24 Underfrequency Load Shedding
1180 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018

Other manuals for Siemens 6MD86

Related product manuals