09.02  Connection 
Siemens AG    6SE7087-6AK85-1AA0 
3-7 
Rectifier/Regenerating Unit    Operating instructions 
Unit  Mains supply fuses 
Order No.  Column 1  Column 2 
  Siemens (SITOR) 
 
Bussmann 
US standard 
6SE70  A  Type  A  Type 
22-1EC85-1AA0 32 3NE4101  40  170M3608 
24-1EC85-1AA0 63 3NE4118  63  170M3610 
28-6EC85-1AA0 125 3NE4122  125  170M3613 
31-7EE85-1AA0 250 3NE3227  250  170M3616 
32-2EE85-1AA0 315 3NE3230-0B 315  170M3617 
33-1EE85-1AA0 450 3NE3233  450  170M3620 
33-8EE85-1AA0 450 3NE3333  550  170M3622 
34-6EE85-1AA0 560 3NE3335  700  170M4617 
36-1EE85-1AA0 800 3NE3338-8  900  170M5615 
22-7FC85-1AA0 40 3NE4102  50  170M3688 
24-1FC85-1AA0 63 3NE4118  63  170M3689 
27-2FC85-1AA0 100 3NE4121  125  170M3692 
28-8FC85-1AA0 125 3NE3222  160  170M3693 
31-5FE85-1AA0 160 3NE3224    — 
32-4FE85-1AA0 315 3NE3230-0B    — 
32-7FE85-1AA0 350 3NE3231  400  170M4693 
33-5FE85-1AA0 450 3NE3333  550  170M6693 
34-2FE85-1AA0 500 3NE3334-0B    — 
35-4FE85-1AA0 630 3NE3336  800  170M6696 
31-4HE85-1AA0 160 3NE3224    — 
32-2HE85-1AA0 315 3NE3230-0B  350  170M6689 
32-7HE85-1AA0 350 3NE3231    — 
34-2HE85-1AA0 560 3NE3335    — 
35-3HE85-1AA0 630 3NE3336  800  170M6696 
 
Table 3.3  Recommended mains fuses 
 
Table 3.3:  Semiconductor protection only, lines are not reliably protected 
 
CAUTION 
Devices of sizes C and E require semiconductor protection fuses in the network incoming line to protect the 
semiconductors according to Table 3.3. For devices with integrated arm-circuit fuses (sizes H and K – see 
Table 3.5), no semiconductor protection is required outside the device. 
Line protection must be ensured for all device types by assigning a suitable line protection element (e.g. fuse, 
line protection circuit-breaker) to the line cross-sectional area as defined in the currently valid standards – e.g. 
DIN VDE 0100 Part 430. 
 