09.02  Fault and Alarm Messages 
Siemens AG    6SE7087-6AK85-1AA0 
7-7 
Rectifier/Regenerating Unit    Operating Instructions 
Fault 
No. 
Fault description 
Fault 
value 
Meaning  Possible causes 
Countermeasures 
F082 TB/CB Telegr 
TB/CB telegram failure 
 
The exchange of data has been 
interrupted. 
 
P695 defines the telegram failure time 
1 
2 
3 
4 
5 
 
6 
7 
8 
 
9 
10 
11 
 
12 
 
21 
22 
CB alarm channel faulty 
TB alarm channel faulty 
TB error channel faulty 
CB task channel (CB 
→ CUR) faulty
CB answer channel (CUR 
→ CB) 
faulty 
Internal error 
TB task channel (TB 
→ CUR) faulty 
TB answer channel (CUR 
→ TB) 
faulty 
Internal error 
CB/TB Telegram failure 
PMU task channel (CUR 
→ TB) 
faulty 
PMU answer channel (TB 
→ CUR) 
faulty 
CB/TB setpoint channel faulty 
CB/TB actual value channel faulty 
- 
F090  Circuit ID F 
Circuit identification not possible 
1  If generating mode is inhibited 
(P076 = xx1), circuit identification is 
not possible! 
- Set P076 = x2 
 
 2 
If 
α = 30°, not enough rectifier 
current flows (less than 25% of the 
rated DC current with 
P160=150.0% or less than 10% 
with P160=60.0%) 
- Connection to DC link interrupted 
 
  3  P141 (Rectifier Induct.) and/or 
P143 (Inverter Induct.) and/or P144 
(C for DC link) could not be 
identified 
- Commutating inductance too low 
(see Section 3.1) 
- Connection to DC link interrupted 
 
  4  A waiting time of 20s has already 
elapsed but the circuit identification 
cannot be carried out because the 
DC link voltage is too high 
(Ud>20% of 1.35
*
P071) 
- Another unit is supplying the DC 
link 
- Wait until the DC link has 
discharged sufficiently, then start 
circuit identification again 
F091  Circuit ID C 
Circuit identification or forming aborted 
due to external cause. 
 
If circuit identification is aborted, only 
those parameters are modified whose 
assignment was completed before this 
fault occurred. 
1 
 
 
 
 
2 
 
 
 
3 
 
4 
 
 
 
 
5 
The abort took place because the 
RUN or "R" status was exited for 
some reason (e.g. brief power 
outage) during forming or circuit 
identification. 
The abort took place because the 
reserve data set selection changed 
during forming or circuit 
identification. 
The abort took place because the 
OFF command was given. 
The abort took place because an 
ON command was not given within 
20 sec after selecting the forming 
function (P052=20) or the circuit 
identification function (P052=21) 
The abort took place because the 
"Inhibit regenerating" command 
was given during circuit 
identification (see control word 1, 
bit 12 and P572) 
- 