Figure 6-11 Configuration Tab, Event Records, Voltage Event
Configure the respective parameters according to the following table.
Table 6-8 Settings for Voltage Events
Parameter Default Setting Setting Range
Voltage Event
Swell threshold
12
110 % 105 % to 140 %, increments of 5 %
Dip threshold
12
90 % 75 % to 95 %, increments of 5 %
Interruption threshold 5 % 1 %, 2 %, 3 %, 5 %, 8 %, 10 %
Hysteresis 2 % 1 % to 6 %, increments of 1 %
After the parameterization, click Send.
In the navigation window, click Activation and cancel.
Enter the activation password (refer to Table 2-3).
Click Activation.
Value View of the Voltage Events
To display the values of the voltage events in the Value view tab, proceed as follows:
In the navigation window, click Events.
The information of the latest 20 voltage events is shown without query.
12
According to the EN 50160 standard in the PQ report, the default setting of dip and swell (90 % and 110 %) is recommended.
Power Quality
6.4 Event Records
SICAM, SICAM P850/P855 7KG85X, Manual 127
E50417-H1040-C482-A9, Edition 03.2022