EasyManua.ls Logo

Siemens 7KG85 Series - Environmental Conditions and Climatic Stress Tests

Siemens 7KG85 Series
281 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface RS485
Connection Terminal side, 9-pin D-sub socket
Protocol Refer to 13.2.5.1 Communication Serial
Baud rate (adjustable) Modbus RTU (optional):
Min. 1200 bit/s
Max. 115 200 bit/s
IEC 60870-5-103 (optional):
Min. 9600 bit/s
Max. 38 400 bit/s
Maximum distance of transmission Max. 1 km
(depending on transmission rate)
Transmission level Low: -5 V to -1.5 V
High: +1.5 V to +5 V
Reception level Low: ≤ -0.2 V
High: ≥ +0.2 V
Bus termination Not integrated, bus termination using plugs with inte-
grated bus terminating resistors.
Pin No. Assignment
1 Shield
2 Not assigned
3 A
RS485 connection pin A
4 Not assigned
5 GND
(towards DC +5 V)
6 DC +5 V
Supply voltage for terminating resistors (max. 100 mA)
7 RTS
Direction control
(if required for an external conversion)
8 B
RS485 connection pin B
9 Not assigned
Environmental Conditions and Climatic Stress Tests
Environmental Conditions
Temperature data
Operating temperature
Devices with display: the legibility
of the display is impaired at
temperatures < 0 °C (+32 °F)
-25 °C to +55 °C
-13 °F to +131 °F
Temperature during transport -40 °C to +70 °C
-40 °F to +158 °F
Temperature during storage -40 °C to +70 °C
-40 °F to +158 °F
Maximum temperature gradient 20 K/h
12.1.4
Technical Data
12.1 Technical Data
248 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022

Table of Contents

Other manuals for Siemens 7KG85 Series

Related product manuals