Configuration via Web Pages
Configuration of the IEC 61850 Protocol
To change the IEC 61850 settings in the Configuration tab, proceed as follows:
In the navigation window, click Communication Ethernet.
Select IEC 61850 as the Bus protocol.
[sc_communication_IEC_61850, 1, en_US]
Figure 2-31
Configuration Tab, IEC 61850 Settings
Configure the respective parameters according to the following table.
Table 2-20
Settings for IEC 61850
Parameter Default Setting Setting Range
IED Name SICAM_P850/P855_01 Any, max. 60 characters
Only a-z, A-Z, _, 0-9 are permitted.
The first character must be an alpha character.
Voltage - Dead band 5 % 1 % to 5 %, in 1 % steps
Current - Dead band 5 % 1 % to 5 %, in 1 % steps
Power - Dead band 5 % 1 % to 5 %, in 1 % steps
Power factor - Dead band 5 % 2 % to 5 %, in 1 % steps
2.6.3.2
Basic Functions
2.6 Ethernet Communication
70 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022