Example: 4-Wire Network, 3 Voltage Transformers and 3 Current Transformers, Unbalanced
[dw_4w_3vt_3ct_unbln, 1, --_--]
Figure 9-13
Example: 4-Wire Network, 3 Voltage Transformers and 3 Current Transformers, Unbalanced
i
i
NOTE
If you need to change the direction of the current connection, you can configure the current inverse for
each phase in Configuration > Basic configuration > AC measurement.
Commissioning and First Steps
9.6 Connection Principle
SICAM, SICAM P850/P855 7KG85X, Manual 205