[sc_communication_modbus_TCP, 1, en_US]
Figure 2-28
Configuration Tab, Modbus TCP Settings
Configure the respective parameters according to the following table.
Table 2-19
Settings for Modbus TCP
Parameter Default Setting Setting Range
Standard port number 502 502
Not settable
Access rights Full Full
Read only
User-defined port 1 No No
Yes
Port number
5
503 503 to 65 535
Access rights
5
Read only Full
Read only
Port number 504 503 to 65 535
Access rights Read only Full
Read only
5
This parameter is available only if User-defined port 1 is set to yes.
Basic Functions
2.6 Ethernet Communication
66 SICAM, SICAM P850/P855 7KG85X, Manual
E50417-H1040-C482-A9, Edition 03.2022