SMART 7KT0310 Manual
Parameterization with function keys
Cong.
page
Function Range or Selection
Factory
Setting
Password 0000to9998 1000
1 ChangePassword No/Yes No
1.1 NewPassword 0000to9998 1000
2 Network
Selection
3P4W,3P3W,1P2W-P1,
1P2W-P2and1P2W-P3
3P4W
3 CTSecondary 1Aor5A 5
4 CtPrimary 1A,5Ato10,000A 5
5 PtSecondary 100Vto500V 350
6 Ptprimary 100Vto500kV 350
7 SlaveId 1to255 1
8 Baud Rate 300,600,1200,2400,
4800,9600and19200
(bps)
9600
9 Parity None,Odd,Even None
10 Stop Bit 1 or 2 1
11 BackLight 0 to 7200 sec. 0000
12 Demandinterval
method
Sliding/Fixed Sliding
13 Demandinterval
duration
1 to 30 15
14 Demandinterval
length
1 to 30 min 1
15 MaxPageAuto 1 to 22 22
16 ChangePage
Sequence
No/Yes No
16.01 Pagesequence1 1 to 22 1
16.02 Pagesequence2 1 to 22 2
16.03 Pagesequence3 1 to 22 3
16.04 Pagesequence4 1 to 22 4
16.05 Pagesequence5 1 to 22 5
16.06 Pagesequence6 1 to 22 6
16.07 Pagesequence7 1 to 22 7
16.08 Pagesequence8 1 to 22 8
16.09 Pagesequence9 1 to 22 9
16.10 Pagesequence10 1 to 22 10
Cong.
page
Function Range or Selection
Factory
Setting
16.11 Pagesequence11 1 to 22 11
16.12 Pagesequence12 1 to 22 12
16.13 Pagesequence13 1 to 22 13
16.14 Pagesequence14 1 to 22 14
16.15 Pagesequence15 1 to 22 15
16.16 Pagesequence16 1 to 22 16
16.17 Pagesequence17 1 to 22 17
16.18 Pagesequence18 1 to 22 18
16.19 Pagesequence19 1 to 22 19
16.20 Pagesequence20 1 to 22 20
16.21 Pagesequence21 1 to 22 21
16.22 Pagesequence22 1 to 22 22
17 Factory default No/Yes No
18 Resetenergyand
MAX demand
No/Yes No
18.1 Password 0001to9999 1001
18.01
1)
Resetactive
energy
No/Yes No
18.02 Resetreactive
energy
No/Yes No
18.03 Reset apparent
energy
No/Yes No
18.04 Reset MAX No/Yes No
18.05 ResetONhour No/Yes No
NETWORK SELECTION and WIRING INPUT
Network selection in
conguration mode
Wiring
3P4W 3P4W,2P3W
3P3W 3P3W
1P2W(P1/P2/P3) 1P2W(P1/P2/P3)
Note:P1,P2andP3areThreePhase.
1) Forresettingenergyparametersuserwillbepromptedthe
password.Ifcorrectpasswordisentered,theuserwillbeableto
resetallenergyparameters.Thispasswordwillbevaluewhich
willbegreaterthanthecongurationpasswordby1.