15
SMART 7KT0310 Manual
Communication
Protocol and interface
Protocol:ModbusRTU
Interface:IntegratedRS485interface
Communication parameters
Communicationaddress 1to255
Transmission mode Halfduplex
Data types FloatandInteger
Transmission distance 500mmaximum
Transmission Speed 300,600,1200,2400,4800,
9600,19200(inbps)
Parity None,Odd,Even
Stop bits 1 or 2
Response Time 100msMax&Independent,at
Baud rate
Connection diagram for communication
RS485-RS232
Converter
Master
Suggested
terminating resistor
(120 ohm,¼watt)
F2
F3 F4
F1
F2
F3 F4
F1
F2
F3 F4
F1
ContactsalesforPCbasedmonitoringsoftwareto
communicatewiththemeters.
Modbus register addresses list
Readable Parameters: [Length (Register): 2; Data Structure: Float]
Address Hex Address Parameter
30000 0x00 VoltageV1N
30002 0x02 VoltageV2N
30004 0x04 VoltageV3N
30006 0x06 AverageVoltageLN
30008 0x08 VoltageV12
30010 0x0A VoltageV23
30012 0x0C VoltageV31
30014 0x0E AverageVoltageLL
30016 0x10 CurrentI1
30018 0x12 CurrentI2
30020 0x14 CurrentI3
30022 0x16 AverageCurrent
30024 0x18 kW1
30026 0x1A kW2
30028 0x1C kW3
30030 0x1E kVA1
30032 0x20 kVA2
30034 0x22 kVA3
30036 0x24 kVAr1
Address Hex Address Parameter
30038 0x26 kVAr2
30040 0x28 kVAr3
30042 0x2A TotalKW
30044 0x2C Total KVA
30046 0x2E Total KVAr
30048 0x30 PF1
30050 0x32 PF2
30052 0x34 PF3
30054 0x36 AveragePF
30056 0x38 Frequency
30058 0x3A TotalnetkWh
30060 0x3C TotalnetkVAh
30062 0x3E TotalnetkVArh
30064 0x40 kWMaxActivePower
30066 0x42 kWMinActivePower
30068 0x44 kVArMaxReactivePower
30070 0x46 kVArMinReactivePower
30072 0x48 kVAMaxApparentPower
30084 0x54 kWh1(Imp)