$SSHQGL[6$
9
&* &
Annunciations 7SA513 for PC, LC-display and binary inputs/outputs
²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²²
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
M : Measurand
E - Earth fault annunciation
IOT - I: can be marshalled to binary input
O: can be marshalled to binary output (LED, signal relay)
T: can be marshalled to trip relay
¿©©©©§©©©©©©©©©©©©©§©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©§©©§©©§©§©©©¤
FNo.Abbreviation Meaning OpFtEIOT
¨©©©©ª©©©©©©©©©©©©©ª©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©ª©©ª©©ª©ª©©©
3>Time Synchro>Time synchronization IO
4>Start FltRec>Start fault recording C IO
5>LED reset >Reset LED indicators IO
7>ParamSelec.1>Parameter set selection 1 (with No.8) IO
8>ParamSelec.2>Parameter set selection 2 (with No.7) IO
11>Annunc. 1 >User defined annunciation 1 CG IOT
12>Annunc. 2 >User defined annunciation 2 CG IOT
13>Annunc. 3 >User defined annunciation 3 CG IOT
14>Annunc. 4 >User defined annunciation 4 CG IOT
15>Sys-Test >Testing via system-interface IO
16>Sys-MM-block>Block. of monitoring dir. via sys.-int IO
51Dev.operativeDevice operative / healthy CG O
52Prot. operat.Any protection operative CG O
56Initial startInitial start of processor system C
60LED reset LED Reset C O
61LogMeasBlock Logging and measuring functions blockedCG
62Test mode Test mode CG
95Param.runningParameters are being set CG O
96Param. Set A Parameter set A is active CG O
97Param. Set B Parameter set B is active CG O
98Param. Set C Parameter set C is active CG O
99Param. Set D Parameter set D is active CG O
100Wrong SW-versWrong software-version C
101Wrong dev. IDWrong device identification C
110Annunc. lost Annunciations lost (buffer overflow) C
111Annu. PC lostAnnunciations for PC lost C
115Flt.Buff.OverFault annunciation buffer overflow C
120Oper.Ann.InvaOperational annunciations invalid CG
121Flt.Ann.InvalFault annunciations invalid CG
123Stat.Buff.InvStatistic annunciation buffer invalid CG
124LED Buff.InvaLED annunciation buffer invalid CG
129VDEW-StateInvVDEW state invalid CG
135Chs Error Error in check sum CG
136Chs.A Error Error in check sum for parameter set A CG
137Chs.B Error Error in check sum for parameter set B CG
138Chs.C Error Error in check sum for parameter set C CG
139Chs.D Error Error in check sum for parameter set D CG
141Failure 24V Failure of internal 24 VDC power supplyCG OT
143Failure 15V Failure of internal 15 VDC power supplyCG OT
144Failure 5V Failure of internal 5 VDC power supply CG OT
145Failure 0V Failure of internal 0 VDC power supply CG OT
154Fail. TripRelSupervision trip circuit CG
159LSA disruptedLSA (system interface) disrupted CG
161I supervisionMeasured value supervision of currents O
162Failure ÉI Failure: Current summation supervision CG OT
163Failure IsymmFailure: Current symmetry supervision CG OT
¥©©©©¦©©©©©©©©©©©©©¦©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©¦©©¦©©¦©¦©©©¾