9

&*&
1135 T-CLOSE Maximum close command duration
min. 0.01 s
max. 32.00 ©©©©
1136 3-P. COUPL 3 pole coupling
WITH FAULT DETEC [ ] With fault detection
WITH TRIP COMM. [ ] With trip command
1137 TRIP2phFLT Trip type with 2phase faults
THREE-POLE [ ] Three-pole
1-POLE LEADING [ ] 1-pole leading
1-POLE LAGGING [ ] 1-pole lagging
1138 LOAD COMP. Load compensation
NO []no
YES [ ] yes
1140 I-RESID. Current threshold for open line detect. I-RES
min. 0.05 I/In
max. 1.00 ©©©©
1141 U-RESID. Voltage threshold for open line detect. U-RES
min. 2 V
max. 70 ©©©©
1142 T-CL-PROL CB close zone release extension
min. 0.01 s
max. 32.00 ©©©©
1143 CB COND. Checking of circuit breaker position
I< AND U< [ ] I-RES.< and U-RES.<
CB AUX AND I< [ ] CB aux. and I-RES.<
1145 T-M/C-PROL Prolongation time after manual closing
min. 0.01 s
max. 32.00 ©©©©
1149 T-EXT.STAB Stabilization time for external trip
min. 0.00 s
max. 32.00 ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1200 DIST.PROT. GENERAL SETTINGS
1201 DIST.PROT. Distance protection function
ON []on
OFF [ ] off
1202 DIR. FD&T4 Direction for fault detection directional trip
FORWARDS [ ] Forwards
REVERSE [ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1203 T4 Delay T4 fault detection directional trip
min. 0.00 s
max. 32.00/Ñ ©©©©
1204 T5 Delay T5 fault detection non-directional trip
min. 0.00 s
max. 32.00/Ñ ©©©©