$SSHQGL[6$
9
&* &
1400 DIST.PROT. CONTROLLED ZONES
1401 R1B Zone 1B: Resistance (phase-phase) R1B
min. 0.05 Ï
max. 65.00 ©©©©
1402 X1B Zone 1B: Reactance (reach) X1B
min. 0.05 Ï
max. 200.00 ©©©©
1403 R1BE Zone 1B: Resistance (phase-earth) R1BE
min. 0.05 Ï
max. 130.00 ©©©©
1404 DIREC. Z1B Zone 1B: Direction
FORWARDS [ ] Forwards
REVERSE [ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1405 T1B 1PHASE Zone 1B: Delay for single phase faults T1B 1PH
min. 0.00 s
max. 32.00/Ñ ©©©©
1406 T1B >1PHAS Zone 1B: Delay for multi-phase faults T1B
min. 0.00 s
max. 32.00/Ñ ©©©©
1407 TBLK DELAY Coord.-Timer for blocking scheme
min. 0.000 s
max. 1.000 ©©©©
1411 R1L Zone 1L: Resistance (phase-phase) R1L
min. 0.05 Ï
max. 65.00 ©©©©
1412 X1L Zone 1L: Reactance (reach) X1L
min. 0.05 Ï
max. 200.00 ©©©©
1413 R1LE Zone 1L: Resistance (phase-earth) R1LE
min. 0.05 Ï
max. 130.00 ©©©©
1414 DIREC. Z1L Zone 1L: Direction
FORWARDS [ ] Forwards
REVERSE [ ] Reverse
NON-DIRECTIONAL [ ] Non-directional
1415 T1L Zone 1L: Delay for all faults T1L
min. 0.00 s
max. 32.00/Ñ ©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
1500 DIST.PROT. FAULT DETEC.PROG
1501 PROG.U/I/phi Fault detection program U/I/phi
LE:Uphe/LL:Uphph [ ] LE:Uphe/LL:Uphph
LE:Uphph/LL:Uphp [ ] LE:Uphph/LL:Uphp
LE:Uphe/LL:Uphe [ ] LE:Uphe/LL:Uphe